ZING²
/Tools
Chat
Project Soon
Tools
PricingLogin
HomeChat
Project (Soon)
Tools
Dashboard
ROUGH-IN
Conduit Bending Calculator
Conduit Fill & Raceway Sizing Calculator
Junction Box Fill Calculator (NEC 314.16)
Ethernet & PoE Calculator
WIRING
Wire Size Calculator
Wire Ampacity & Derating Calculator (NEC 310.16)
Voltage Drop Calculator (AC & DC)
Grounding Electrode Conductor (GEC) Calculator
Circuit Breaker & Fuse Sizing Calculator
POWER & PLANNING
Residential Service Load Calculator
Transformer Sizing Calculator (kVA & Amps)
Lighting Layout & Spacing Calculator
Ohm's Law Calculator
UTILITIES
Construction Math Calculator
Motor FLA & Protection Calculator (NEC Art. 430)
Circuit Breaker & Fuse Sizing Calculator
NEC 2020 Code Search & Lookup
Reference Charts
310.16: Conductor Ampacities (Quick Reference)NEC Table 310.16: Allowable Ampacities (Full)250.66: Grounding Electrode Conductor (GEC) - Standardized Parallel RulesNEC Table 250.102(C)(1): Bonding Jumper Sizing300.5: Minimum Burial Depth (Quick Reference)300.5: Minimum Cover Requirements (Full)NEC Table 314.16(A): Metal Box Fill CapacitiesNEC Table 250.122: Equipment Grounding ConductorsNEC Table 310.15(B)(1): Temp Correction (30°C)NEC Table 310.15(C)(1): Wire Adjustment FactorsNEC Chapter 9 Table 8: Conductor PropertiesNEC Chapter 9 Table 4: EMT Dimensions & FillNEC Chapter 9 Table 4: PVC Schedule 40 FillNEC Chapter 9 Table 4: PVC Schedule 80 FillNEC Chapter 9 Table 4: RMC Dimensions & FillNEC Table 314.16(B): Volume Allowance
Zing² Reference
Loading Preset...
ZING2

Electrical Code Simplified.
Built for the trade.

FacebookFacebookRedditr/Zing2

Platform

About UsContact UsBecome a PartnerPro DirectoryTopic HubsBlogPricingTerms of ServiceSitemap

Calculators & Tools →

Conduit Bending CalculatorConduit Fill CalculatorVoltage Drop CalculatorLoad CalculatorMotor FLA & ProtectionAmpacity CalculatorTransformer Sizing CalculatorGrounding & Bonding CalculatorCircuit Breaker & Fuse SizingJunction Box Fill CalculatorWire Wizard CalculatorLighting Layout CalculatorOhm's Law CalculatorNEC 2020 Code SearchEthernet & PoE CalculatorScientific Calculator

NEC Reference Tables →

310.16: Conductor Ampacities250.66: Grounding (GEC)250.122: Equipment Grounding250.102(C)(1): Bonding Jumper310.15(B)(1): Temp. Correction310.15(C)(1): AdjustmentCh 9 Table 8: PropertiesCh 9 Table 4: Conduit Fill314.16(A): Box Fill300.5: Minimum Burial Depth

Zing² Software Solutions

Los Angeles, CA

Support: [email protected]
Phone: (626) 784-5772

© 2026 Zing². Not affiliated with NFPA.

Home
Tools
Motor FLA & Protection Calculator (NEC Art. 430)
Zing2 Logo

1HP Sump Pump Circuit

Size conductors, breakers, and overload protection for safe motor operation.

Motor branch circuits require specific sizing rules to handle inrush currents and protect windings. This calculator uses NEC Tables 430.248 & 430.250 for Full Load Current (FLC), and applies multipliers for Short Circuit Ground Fault (SCGF) protection and Overload protection.

Important: Wire and Short Circuit Protection are based on NEC Table FLC. Overload protection is based on Nameplate FLA (if provided).

1Motor Specifications

-
-

2Protection & Overload

-
-

Calculation Summary
Based on NEC Table 430.248 (Single-Phase) or Table 430.250 (Three-Phase). The FLC is used to size branch circuit conductors and short-circuit protection.

-Amps
NEC 430.250

Breaker

Short Circuit Protection

15 Amps

Max 250% of FLC (NEC 430.52). Rounded up to next standard size.

Wire Size

Branch Circuit

14 AWG

Min 125% of FLC (2.6A). Based on 75°C column.

NEMA Starter

Motor Controller

N/A

Standard NEMA size for 1 HP @ 460.

Overload

Heater Setting

2.6 Amps

125% of Table FLC.

Popular motor control Configurations

1HP 115V Single Phase Motor Calc10HP 460V 3-Phase Motor Calc5HP Air Compressor Circuit Size1HP Sump Pump Circuit

Motor Sizing Formula

Ibranch = 1.25 × Total FLC
Ioverload = Inameplate × Service Factor

NEC Article 430

Article 430 covers motors. Table 430.248 (1-phase) and 430.250 (3-phase) provide FLC currents. 430.52 dictates maximum short-circuit and ground-fault protection settings.

Frequently Asked Questions

Do I use nameplate amps or NEC table amps?

For sizing conductors and short-circuit protection (breakers/fuses), you MUST use NEC Table values. For sizing Overload protection (heaters), you use the Nameplate current.

What size breaker do I need for a motor?

Inverse time breakers are typically allowed up to 250% of the motor's FLC per Table 430.52 to handle inrush current without nuisance tripping.

What size wire do I need for a motor?

Conductors supplying a single motor must have an ampacity of at least 125% of the motor's FLC Rating (NEC 430.22).