CH 3
310.15(B)(1)

Temp Correction (30°C)

NEC 2020 • 2023 • 2026 COMPLIANT

Multipliers for ampacity based on ambient temperature variations.

Ambient Temp (°C)Ambient Temp (°F)60°C75°C90°C
10 or less50 or less1.291.201.15
11 - 1551 - 591.221.151.12
16 - 2060 - 681.151.111.08
21 - 2569 - 771.081.051.04
26 - 3078 - 861.001.001.00
31 - 3587 - 950.910.940.96
36 - 4096 - 1040.820.880.91
41 - 45105 - 1130.710.820.87
46 - 50114 - 1220.580.750.82
51 - 55123 - 1310.410.670.76
56 - 60132 - 140-0.580.71
61 - 65141 - 149-0.470.65
66 - 70150 - 158-0.330.58
71 - 75159 - 167--0.50
76 - 80168 - 176--0.41

Professional Usage Disclaimer

This data is provided for informational purposes only. Always verify with the latest edition of the National Electrical Code (NFPA 70) and consult with a licensed electrical professional or AHJ (Authority Having Jurisdiction) before performing any electrical work. Zing² is a reference tool, not a substitute for qualified engineering.

Professional Field Notes & Gotchas

  • Standard Ambient: All Table 310.16 values are based on an ambient temperature of 30°C (86°F). Anything hotter requires the multipliers from this table.
  • Rooftop Rule (Deleted): Note that the old 'Rooftop Distance' temperature adder (RAC) was removed in recent NEC cycles. You now use the actual ambient temperature unless specific local codes apply.
  • Compounding Factors: If you have a rooftop run with high ambient heat AND more than 3 wires, you must multiply the factors from and 310.15(C)(1) together.
  • The Cold Factor: Use these values to INCREASE ampacity in cold storage or freezer applications, though you can never exceed the terminal rating.

NEC 2023 vs 2026: What changed?

NEC 2023 vs 2026: The table remains mathematically identical, but the cross-references to 310.16 were updated for clarity. The 2026 code reinforces using localized weather data for more accurate ambient calculations.

Technical FAQs

What is the temperature correction for 100°F?

At 100°F (38°C), 90°C wire (THHN) has a multiplier of 0.91. This means your 100A wire is now only safe for 91A.

Do I need to derate for attic heat?

Absolutely. Attics often exceed 114°F, which requires a multiplier of 0.82 for 90°C conductors. High attic temperatures are a leading cause of nuisance breaker tripping.

Which column do I use for THHN?

For THHN wire, utilize the 90°C column for the correction factor. However, ensure the final adjusted ampacity doesn't exceed the 75°C terminal rating.